400kva Oil immersed power isolation transformer
Application environment
Altitude: less than 1000m
Ambient temperature: the highest temperature +40°C;
The highest monthly mean temperature +30°C;
The lowest temperature: -10°C;
The highest yearly mean temperature: +20°C
Rated capacity: 400KVA
Voltage Schedule: HV: 6, 6.3, 10, 10.5, 11
Tapping: more or less 5%(more or less 2*2.5%)
LV: 0.4
Vector Group: Yyn0, Dyn11
Consumption(W): Noload(Kw)800, load(kw)4300
No load current(%): 1.0
Short circuit impedance(%): 4
Weight: Body(880kg), Oil(205kg), total(1310kg)
Outline dimension: (L*W*H): 1435mm*820mm*1460mm
Gauging distance: 660mm*660mm
400KVA Power Transformer